Title of article :
Evaluation of the Operational Condition and Reliability of Surge Arresters Used on Medium Voltage Networks
Author/Authors :
K. Kannus and K. Lahti، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Abstract :
Laboratory studies were conducted on gapped siliconcarbide
arresters and gapless metal-oxide surge arresters (MOAs)
gathered from 24 kV networks in Finland. A total of 410 arresters
of 21 different types from eight different manufacturers were investigated.
A total of 246 silicon-carbide arresters (age from 14 to
38 years) and 164 MOAs (age from 4 to 15 years) were studied at
the High Voltage Laboratory of Tampere University of Technology.
The results of the measurements on MOAs were compared to the
measurements conducted earlier on 16 new, unused MOAs of the
same types as those taken from the field. A portion of 16.7% (41
specimens) of the silicon-carbide arresters failed in the ac voltage
withstand test and 34.5% (85 specimens) did not pass the lightning
impulse sparkover test. The current impulse test of the silicon-carbide
arresters resulted in a lot of damage. Due to the damage and
failures in the electrical tests the authors recommend the electricity
companies in Finland to exchange 7 types of silicon-carbide arresters
to new MOA types in order to reduce the risk of arrester
failures and to improve the protection levels in MV networks. All
the ten MOA types studied were generally in good condition after
being used 4–15 years in networks. Only three specimens (out of
164) could be evaluated to be faulty. Comparisons between the
MOAs gathered from the networks and the unused MOAs showed
that the protection levels of the MOA types studied had remained
stable and the ac durability of these MOA types had not remarkably
weakened during the use in networks.
Keywords :
Metal oxide surge arrester , silicon-carbide arrester , surge arrester. , Medium voltage network
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY