Title of article :
Optimal Calculation of Impedance of an Auxiliary Loop to Mitigate Magnetic Field of a Transmission Line
Author/Authors :
A. R. Memari، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Abstract :
This paper deals with the process of achieving zero
mitigated magnetic field at any point of consideration from center
of right of way by implementing an auxiliary loop beneath the
outer phases of an existing active conductors. For numerical
demonstration, a flat configuration of 750-kV transmission line
is utilized. Flux induced by the active conductors in the loop is
calculated and henceforth the obtained current flowing along the
auxiliary loop causes magnetic field, which fully opposes the one
originated by the conductors. At the same time, interaction of
magnetic field originated by the transmission line at other points
with that of the loop also results in noticeable mitigation at the
points.
Keywords :
Auxiliary loop , loop current , magnetic field , mitigation , Transmission Line.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY