Title of article
Electric Field Analysis of Water Drop Corona
Author/Authors
Z. Guan، نويسنده , , L. Wang، نويسنده , , B. Yang، نويسنده , , X. Liang، نويسنده , , and Z. Li، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
6
From page
964
To page
969
Abstract
Water drops on surface of polymer insulation materials
may cause corona because they can enhance the electric field
nearby. Water drop corona plays an important negative role in
the long-term performance of composite insulators. In this paper,
based on a model with two parallel electrodes water drop corona
is studied. The relationship between initial corona voltage and different
sets of water drops is obtained from experiments. Then several
factors, which may affect the electric field analysis of water
drop corona, are studied by numerical calculation on computer.
Calculation is mainly on a 2-D model. However, a 3-D model is also
used to study the effect of water drops distributed in space.
Keywords
Composite insulation , Corona , electric fields , numericalanalysis.
Journal title