Title of article :
Power System Harmonic Analysis Using State-Estimation Method for Japanese Field Data
Author/Authors :
N. Kanao، نويسنده , , and M. Yamashita، نويسنده , , H. Yanagida، نويسنده , , M. Mizukami، نويسنده , , Y. Hayashi، نويسنده , , and J. Matsuki، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
8
From page :
970
To page :
977
Abstract :
The harmonic state-estimation (HSE) method appears to be effective but its applicability has yet been fully verified using actual data in power systems. Particularly in Japan, there has been no verification of the applicability of the method in actual power systems. In this paper, for Japanese field data synchronized with a Global Positioning System (GPS) clock, a practical method for power system harmonic analysis is proposed, which is based on HSE. In the proposed method, in order to improve the precision of HSE, uncertain parameters R, X, and Y of the transmission lines are determined from measured fundamental data, and bad measured harmonic data excluded systematically. It is also possible to estimate the error of each measurement instrument by using HSE. It is confirmed that by using only partial and selected measurement data synchronized with a GPS clock, the entire harmonic distribution of the actual power system has been obtained effectively. In this paper, field-test results of the HSE on an actual Japanese power system are shown. Furthermore, an example of harmonic analysis based on HSE in the actual power system is presented, which is prediction of harmonic voltage distribution after a change of the actual power system configuration.
Keywords :
power system harmonics , Least-squares methods , Global positioning system , state estimation. , Measurement error
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2005
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400905
Link To Document :
بازگشت