Abstract :
The method of selective harmonic elimination is
often used as an efficient means for obtaining harmonic-reduced
waveforms from voltage sourced converters (VSC). However,
the switching angles required for its implementation are usually
pre-calculated on the basis of a fixed dc bus voltage. In practice,
there are harmonics present in the dc source because of the finite
dc bus capacitance and other realistic operating conditions, which
can potentially introduce additional noncharacteristic harmonics.
This paper examines the harmonic performance of a VSC-based
static synchronous compensator as a function of design and operating
parameters. These include the value of dc capacitor, the
strength of the connected ac network and ac system unbalance.
The results are generated using theoretical analysis for special
cases and numerical simulation using electromagnetic transients
simulation for the more general case.