Abstract :
The load unbalance and the nonlinear loads result
in a significant neutral current in the three-phase four-wire
distribution power system. The Zig-Zag transformer has been
proposed to attenuate the neutral current of the three-phase
four-wire distribution power system. In this paper, an analysis
is carried out and computer simulation is used to evaluate the
performance of the Zig-Zag transformer under ideal and nonideal
power conditions. The simulation results show that (a) the Zig-Zag
transformer can effectively attenuate the neutral current and
zero-sequence harmonic currents on the utility side under the
balanced utility voltage, (b) the utility side neutral current becomes
larger under the unbalanced utility voltage or the distorted utility
voltage with zero sequence harmonic components after applying
the Zig-Zag transformer, (c) the insertion of an inductor in the
utility side of the neutral conductor can alleviate overloading
of the neutral current caused by the unbalanced utility voltages
and the distorted utility voltages with zero sequence harmonic
components.