Title of article :
New tap changing scheme
Author/Authors :
Shuttleworth، نويسنده , , R.; Tian، نويسنده , , X.; Fan، نويسنده , , C.; Power، نويسنده , , A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
5
From page :
108
To page :
112
Abstract :
Tap changers have not changed radically since their invention in the early part of this century. They are slow in operation, typically traversing 19 taps in around 100 seconds, and require frequent maintenance. Previous attempts to devise improved tap changers have concentrated upon thyristor assisted or all solidstate units. For various reasons none of these schemes has been adopted. A new GTO thyristor assisted tap changer is introduced here which addresses the problems of previous schemes. It eliminates excessive conduction losses which are inherent in solid-state tap changers, and at the same time provides a fast response speed by means of fast acting vacuum switches. Calculations show that it will be possible to traverse a 19 tap range in around 0.5s. A unit for a 240MVA transformer will require minimal maintenance as the vacuum switches used in the selector and diverter never make or break more than a few amperes. Test results are given for a 3 kVA transformer and tap changer unit.
Keywords :
TAP CHANGERS , transformers , AC transmission
Journal title :
IEE Proceedings Electric Power Applications
Serial Year :
1996
Journal title :
IEE Proceedings Electric Power Applications
Record number :
402247