Title of article :
Loss-of-mains detection for small generators
Author/Authors :
Barry Hopewell، نويسنده , , P.D.; Jenkins، نويسنده , , N.; Cross، نويسنده , , A.D.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
6
From page :
225
To page :
230
Abstract :
A new loss-of-mains detection method for use with very small generators is proposed. A known load is repeatedly switched on to the supply, and the resulting voltage changes used to estimate the source impedance, and hence to detect loss of mains. Correlating the load switching with the voltage change prevents false operation arising from random load changes. Experiments and simulations are discussed which demonstrate the principles of the technique. Test results are presented which show that the technique operates correctly, and can reliably detect a loss of mains without being susceptible to false tripping.
Keywords :
Small electrical genrrators , Lo , wofmains detection
Journal title :
IEE Proceedings Electric Power Applications
Serial Year :
1996
Journal title :
IEE Proceedings Electric Power Applications
Record number :
402262
Link To Document :
بازگشت