Title of article :
Solid-state on-load transformer tap changer
Author/Authors :
Yousef-Zai، نويسنده , , F.Q.; OʹKelly، نويسنده , , D.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
11
From page :
481
To page :
491
Abstract :
Switching logic is defined for a singlephase transformer tap changer using thyristor switching. A laboratory model validates the theory and shows that tap changing is possible in less than one cycle over the whole power-factor spectrum. Waveform sampling and the use of a microprocessor based control system provides improved control and additional features such as data logging etc. Two schemes are considered for the application of thyristor tap changing to threephase transformers. Economic viability is strongly dependent on the associated power system and its abnormal operating features, namely system fault currents and especially the degree of exposure of the transformer to lightning surges.
Keywords :
Tap changing , Thyristors , transformers
Journal title :
IEE Proceedings Electric Power Applications
Serial Year :
1996
Journal title :
IEE Proceedings Electric Power Applications
Record number :
402294
Link To Document :
بازگشت