Title of article
Eddy current losses and hot-spot evaluation in cover plates of power transformers
Author/Authors
Turowski، نويسنده , , J.; Pelikant، نويسنده , , A.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1997
Pages
6
From page
435
To page
440
Abstract
Heavy current bushings passing
through steel cover plates and housing walls of
power transformers, generators and other large
power equipment are thermally hazardous
elements of construction and a source of
additional power losses. The safety and reliability
of such expensive objects and the safety of power
delivery often depend on the proper design of
these elements. A computer analysis, based on
Maxwell equations and analytical representation
of electromagnetic field has been carried out. The
nonlinear permeability of solid steel was
considered using an analytical approximation.
Eddy current losses have been calculated and
compared using different experimental and
calculation methods. Electromagnetic criteria
were used to forecast possible excessive heating
and hot spots. Various constructional means of
loss and hot spot reduction were considered.
Keywords
Transformers , power losses , hot spot , Eddy current lossa
Journal title
IEE Proceedings Electric Power Applications
Serial Year
1997
Journal title
IEE Proceedings Electric Power Applications
Record number
402351