Title of article
Harmonic analysis of parallel-connected 12-pulse uncontrolled rectifier without an interphase transformer
Author/Authors
Tzeng، نويسنده , , Y.-S.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1998
Pages
8
From page
253
To page
260
Abstract
The author presents a harmonic
analysis of a parallel-connected 12-pulse
uncontrolled bridge rectifier without an
interphase transformer (IPT). Five normal
operating modes of the specific rectifier circuit are
classified, using an analytical method by deriving
instantaneous AC current and DC voltage
waveform equations. The discrete Fourier
transformation algorithm is then carried out to
obtain both current and voltage harmonic
contents. Both the AC current and DC voltage
harmonics for rectifiers with and without an IPT
have been investigated to discuss the influence of
the IPT on rectifier harmonics. Simulation results
reveal that discrepancies in harmonic contents of
both AC current and DC voltage of the two
rectifier circuits are marked. It is noted that, for
extremely light load up to rated load conditions,
the total harmonic distortion (THD) of linesupply
current is reduced, while the THD of DC
output voltage is increased when the IPT is
deleted from rectifier circuit.
Keywords
12-pulse rectifier , RectlJier modelling , Harmonics , Interphase transformer
Journal title
IEE Proceedings Electric Power Applications
Serial Year
1998
Journal title
IEE Proceedings Electric Power Applications
Record number
402393
Link To Document