Title of article :
Harmonic analysis of parallel-connected 12-pulse uncontrolled rectifier without an interphase transformer
Author/Authors :
Tzeng، نويسنده , , Y.-S.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Abstract :
The author presents a harmonic
analysis of a parallel-connected 12-pulse
uncontrolled bridge rectifier without an
interphase transformer (IPT). Five normal
operating modes of the specific rectifier circuit are
classified, using an analytical method by deriving
instantaneous AC current and DC voltage
waveform equations. The discrete Fourier
transformation algorithm is then carried out to
obtain both current and voltage harmonic
contents. Both the AC current and DC voltage
harmonics for rectifiers with and without an IPT
have been investigated to discuss the influence of
the IPT on rectifier harmonics. Simulation results
reveal that discrepancies in harmonic contents of
both AC current and DC voltage of the two
rectifier circuits are marked. It is noted that, for
extremely light load up to rated load conditions,
the total harmonic distortion (THD) of linesupply
current is reduced, while the THD of DC
output voltage is increased when the IPT is
deleted from rectifier circuit.
Keywords :
12-pulse rectifier , RectlJier modelling , Harmonics , Interphase transformer
Journal title :
IEE Proceedings Electric Power Applications
Journal title :