Title of article :
Harmonic domain modelling of high-pulse converters
Author/Authors :
Bathurst، نويسنده , , G.N.; Smith، نويسنده , , B.C.; Watson، نويسنده , , N.R.; Arrillaga، نويسنده , , J.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Abstract :
A technique is described to model phase-shifting converter transformers in the harmonic
domain. The model has been incorporated into a unified Newton solution technique whch permits
solution of hgh-pulse installations with parallel DC connections. A variety of test cases are included
to illustrate the characteristics of a 24-pulse installation under both ideal and non-ideal conditions.
The results show that the characteristic DC harmonics for an individual converter in a multi-pulse
parallel connection installation increase with pulse number rather than decrease as with a series
connection.
Journal title :
IEE Proceedings Electric Power Applications
Journal title :
IEE Proceedings Electric Power Applications