Title of article :
Optimisation-based strategy for shunt active power filter control under non-ideal supply voltages
Author/Authors :
Chang، نويسنده , , G.W.; Yeh، نويسنده , , C.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Abstract :
A new theory and a conceptual design for the three-phase shunt active power filter
(APF) control strategy under imbalanced and distorted supply voltages are presented.
Conventionally, the compensation currents injected by the APF are determined according to
reference frame transformation-based approaches, where the load instantaneous real and reactive
powers are calculated in the new reference frame. The APF injection currents are then computed to
maintain the balanced and sinusoidal source currents, as well as the least active power consumption
by the APF. However, if current harmonics set by harmonic standards or other constraints are
considered, the load harmonic currents after APF compensation can be controlled to meet the
requirements. Therefore, the APF may have an adjustable performance. An optimal algorithm for
the APF control in steady state is proposed, in which the individual and total harmonic current
distortion limits, the minimum load power factor, levels of current imbalance and the size of the
APF can be taken into account. The planned APF does not consume or produce active power and
only the passive energy-storage elements are required in the new APF design. Results obtained by
simulations with Matlab and Simulink show that the proposed approach is more flexible than
conventional approaches for compensating reactive power and harmonic/neutral currents of the
load, even if the source voltages are severely distorted and imbalanced. The new control strategy is
very suitable for planning the APF when several alternative objective functions and constraints are
under considerations.
Journal title :
IEE Proceedings Electric Power Applications
Journal title :
IEE Proceedings Electric Power Applications