Title of article :
Asymmetrical winding configuration to reduce inrush current with appropriate short-circuit current in transformer
Author/Authors :
Chen، نويسنده , , J.-F.; Liang، نويسنده , , T.-J.; Cheng، نويسنده , , C.-K.; Chen، نويسنده , , S.-D.; Lin، نويسنده , , R.-L.; Yang، نويسنده , , W.-H.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
7
From page :
605
To page :
611
Abstract :
A method for transformer design with an asymmetric winding configuration to reduce the inrush current with appropriate voltage regulation and short-circuit current is proposed. Differing from the traditional symmetric winding structure in transformer design, this method can provide the high inrush equivalent inductance and suitable leakage inductance for a transformer. The formulas of the leakage inductance and inrush equivalent inductance are derived for the asymmetric winding configuration. Theoretical analyses showing the desirable winding configuration that the inrush current can be reduced to with appropriate voltage regulation and short-circuit current are presented. Using the inferential result in experiments, the inrush current can be successfully limited under a low voltage regulation and a suitable short-circuit current.
Journal title :
IEE Proceedings Electric Power Applications
Serial Year :
2005
Journal title :
IEE Proceedings Electric Power Applications
Record number :
402793
Link To Document :
بازگشت