Title of article :
Control scheme for reducing rail potential and stray current in MRT systems
Author/Authors :
Liu، نويسنده , , Y.C.; Chen، نويسنده , , J.F.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Abstract :
For reducing the magnitude of stray current, the diode-grounded system is an
improvement over the solidly grounded system, but the rail potential and stray current remain
large. However, since the diode device of this system provides a path for stray current, the
magnitude of the stray current can be easily and conveniently monitored, and positive-pole earth
faults can be inspected. A novel control scheme is proposed. The output voltage of the traction
substation is controlled such that it remains constant in the diode-grounded system, thus the
magnitude of rail potential and stray current can be reduced. Kaohsiung MRT systems are used as
an example of simulating multiple traction substations and multiple trains. The simulation results
show that this novel control scheme can greatly reduce the stray current and rail potential.
Journal title :
IEE Proceedings Electric Power Applications
Journal title :
IEE Proceedings Electric Power Applications