Title of article
Experimental verification of three-phase four-wire current-regulated PWM converter
Author/Authors
Lin، نويسنده , , B.-R.; Yang، نويسنده , , T.-Y.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
9
From page
677
To page
685
Abstract
A bidirectional power flow, three-phase AC/DC converter is presented to implement
power factor correction, regulate the DC-bus voltage and draw balanced and sinusoidal line
currents from AC source. Four switches are adopted in each converter leg to generate a three-level
PWM waveform on the AC terminal to neutral-point voltages. Compared with conventional threephase
three-level converters, the proposed converter has a simpler circuit configuration and fewer
power semiconductors. The classical proportional-integral voltage controller and carrier-based
current controller are adopted in the outer loop and inner loop to implement DC-bus voltage
regulation and current-command tracking, respectively. Simulation and experimental results verify
the validity and effectiveness of the control scheme.
Journal title
IEE Proceedings Electric Power Applications
Serial Year
2005
Journal title
IEE Proceedings Electric Power Applications
Record number
402802
Link To Document