Title of article :
Two-phase controlled compensator for alternatingcurrent quality improvement of electrified railway systems
Author/Authors :
Battistelli، نويسنده , , L.; Lauria، نويسنده , , D.; Proto، نويسنده , , D.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2006
Abstract :
The technological development of electrified railway systems during recent decades has
demanded higher and higher quality performances of the supply subsystem. For this purpose, the
recourse to electronics and to automation techniques can represent the right way to secure a reliable
and efficient electric supply to the railway. The paper summarises the general problems of quality
in railway electrification and proposes a new configuration of traction substations for single-phase
AC-supply railways, based on the use of a two-phase inverter with nonlinear and variable-structure
control system. Such an advanced technical solution allows one to obtain full compensation of load
unbalances, constant load voltage, satisfactory power factor and a remarkable reduction of both
disturbances and nonlinear-load effects. Some numerical applications show the efficacy of the
proposed controlled compensator in containing disturbances and power-parameter variations, as
well as its high performances in terms of fast response time, accuracy in steady-state conditions and
general low sensitivity to disturbances.
Journal title :
IEE Proceedings Electric Power Applications
Journal title :
IEE Proceedings Electric Power Applications