Title of article :
Combined ZVS¿ZCS topology for high-current direct current hybrid switches: design aspects and first measurements
Author/Authors :
Annetje Roodenburg، نويسنده , , B.; Taffone، نويسنده , , A.; Gilardi، نويسنده , , E.; Tenconi، نويسنده , , S.M.; Evenblij، نويسنده , , B.H.; Kaanders، نويسنده , , M.A.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Abstract :
Power electronic switches have been considered for load switching ever since their
invention. This is because semiconductor switches enable fast, arc-less, reliable and maintenancefree
switching. The main disadvantages in relation to conventional switches (i.e. circuit breakers),
however, are their sensitivity to transients, high on-state losses and the presence of leakage current.
The advantages of both types of switches can be exploited by combining the semiconductor and the
mechanical switch and thereby their disadvantages, arc formation and regular maintenance, can
also be eliminated. For hybrid switches (HSs), both zero voltage switching (ZVS) and zero
current switching (ZCS) are frequently used. A new hybrid switching topology has been developed
where both ZVS and ZCS techniques are applied to the mechanical switch. The ‘symbiosis’
between these solid-state switching techniques and a mechanical switch eliminates several of
the disadvantages, resulting in a more reliable direct current (DC) HS that requires less maintenance.
The first turn-off measurement (up to 5 kA) from a prototype that has been developed for
a 3-kV DC grid is presented.
Journal title :
IEE Proceedings Electric Power Applications
Journal title :
IEE Proceedings Electric Power Applications