• Title of article

    The power law character of off-site power failures

  • Author/Authors

    A. John Arul، نويسنده , , C. Senthil Kumar، نويسنده , , S. Marimuthu، نويسنده , , Om Pal Singh، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    8
  • From page
    1401
  • To page
    1408
  • Abstract
    A study on the behavior of off-site AC power failure recovery times at three nuclear plant sites is presented. It is shown, that power law is appropriate for the representation of failure frequency–duration correlation function of off-site power failure events, based on simple assumptions about component failure and repair rates. It is also found that the annual maxima of power failure duration follow Frechet distribution, which is a type II asymptotic distribution, strengthening our assumption of power law for the parent distribution. The extreme value distributions obtained are used for extrapolation beyond the region of observation.
  • Journal title
    Annals of Nuclear Energy
  • Serial Year
    2003
  • Journal title
    Annals of Nuclear Energy
  • Record number

    405831