Title of article :
Estimation of station blackout frequency for Indian fast breeder test reactor
Author/Authors :
M. Ramakrishnan، نويسنده , , A. John Arul، نويسنده , , S. Usha، نويسنده , , C. Senthil Kumar، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
6
From page :
2332
To page :
2337
Abstract :
This paper presents the comparison of station blackout (SBO) frequency computed with approximate time averaged expressions for diesel generator unavailability and time dependent cutset evaluation method. It is found that the frequency of SBO is under predicted by a factor of 2 by approximate time averaged expressions for SBO durations of 8 h and 16 h. The time dependent cutset evaluation method is applied for offsite power feeder outage management by treating the change in SBO frequency when one of the feeders is taken out for maintenance for ‘n’ days, as the risk measure.
Journal title :
Annals of Nuclear Energy
Serial Year :
2008
Journal title :
Annals of Nuclear Energy
Record number :
407969
Link To Document :
بازگشت