Title of article
Diagonal air-distribution system for operating rooms: experiment and modeling
Author/Authors
Monika Woloszyn، نويسنده , , Joseph Virgone، نويسنده , , Stephane Melen، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
8
From page
1171
To page
1178
Abstract
The airflow patterns and the diffusion of contaminants in an operating room with a diagonal air-distribution system were subjected to both experimental measurements and numerical modeling. The experiments were carried out in MINIBAT test cell equipped with an operating table, a medical lamp and a manikin representing the surgeon. Air velocity and tracer-gas concentration were measured automatically at more than 700 points. The numerical simulations were performed using EXP′AIR software developed by Air Liquide for analyzing air quality in operating rooms. Only isothermal conditions were investigated in this comparison with the numerical software. The results showed that the contaminant distribution depended strongly on the presence of obstacles such as medical equipment and staff.
Keywords
Air distribution , Air quality , CFD , Contaminant , Numerical simulation , Experiment , Tracer gas , Operating room , validation
Journal title
Building and Environment
Serial Year
2004
Journal title
Building and Environment
Record number
408827
Link To Document