• Title of article

    Diagonal air-distribution system for operating rooms: experiment and modeling

  • Author/Authors

    Monika Woloszyn، نويسنده , , Joseph Virgone، نويسنده , , Stephane Melen، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    8
  • From page
    1171
  • To page
    1178
  • Abstract
    The airflow patterns and the diffusion of contaminants in an operating room with a diagonal air-distribution system were subjected to both experimental measurements and numerical modeling. The experiments were carried out in MINIBAT test cell equipped with an operating table, a medical lamp and a manikin representing the surgeon. Air velocity and tracer-gas concentration were measured automatically at more than 700 points. The numerical simulations were performed using EXP′AIR software developed by Air Liquide for analyzing air quality in operating rooms. Only isothermal conditions were investigated in this comparison with the numerical software. The results showed that the contaminant distribution depended strongly on the presence of obstacles such as medical equipment and staff.
  • Keywords
    Air distribution , Air quality , CFD , Contaminant , Numerical simulation , Experiment , Tracer gas , Operating room , validation
  • Journal title
    Building and Environment
  • Serial Year
    2004
  • Journal title
    Building and Environment
  • Record number

    408827