• Title of article

    Application of radiant cooling as a passive cooling option in hot humid climate

  • Author/Authors

    Prapapong Vangtook، نويسنده , , Surapong Chirarattananon، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2007
  • Pages
    14
  • From page
    543
  • To page
    556
  • Abstract
    In hot and humid region, air-conditioning is increasingly used to attain thermal comfort. Air-conditioning is highly energy intensive and it is desirable to develop alternative low-energy means to achieve comfort. In a previous experimental investigation using a room equipped with radiant cooling panel, it was found that cooling water kept to 25 °C could be used to attain thermal comfort under some situations, while water at such temperature would not cause condensation of moisture from air on the panel. This paper reports results of a series of whole-year simulations using TRNSYS computer code on applications of radiant cooling to a room model that represents the actual experimental room. Admitting the inability of radiant cooling to accept latent load, chilled water at 10 °C was supplied to cooling coil to precool ventilation air while water cooled by cooling tower was used for radiant cooling in daytime application. For night-time, cooling water from cooling tower supplied for radiant cooling was found to be sufficient to achieve thermal comfort. Such applications are considered to be more amenable to residential houses.
  • Keywords
    Passive cooling , Indirect evaporative cooling , Cooling tower , Radiant Cooling , Thermal comfort
  • Journal title
    Building and Environment
  • Serial Year
    2007
  • Journal title
    Building and Environment
  • Record number

    409298