Application of advanced glazing to high-rise residential buildings in Hong Kong
Author/Authors :
Milorad Bojic ، نويسنده , , Francis Yik، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Pages :
9
From page :
820
To page :
828
Abstract :
The energy saving that can be achieved by applying advanced glazing to a typical high-rise residential building in Hong Kong was evaluated using the simulation software EnergyPlus. It was found that application of low-e glazing would lead to a reduction in cooling electricity use by up to 4.2%. The saving due to application of low-e reversible glazing would be up to 1.9%; double-clear glazing up to 3.7%; and clear plus low-e glazing up to 6.6%. The achievable saving would depend on orientation of building wings, and type and location of rooms. The analysis suggests that for the high-rise public housing blocks in Hong Kong, the use of expensive advanced glazing would not be economically viable from the point of view of saving in cooling energy cost.
Keywords :
Cooling , Low-e glazing , Building envelope