Title of article :
Scale model study of airflow performance in a ceiling slot-ventilated enclosure: Non-isothermal condition
Author/Authors :
Hsin Yu، نويسنده , , Chung-Min Liao، نويسنده , , Huang-Min Liang، نويسنده , , Kuo-Chih Chiang، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Pages :
9
From page :
1142
To page :
1150
Abstract :
Scale-model study of a non-isothermal ceiling slot-ventilated enclosure was investigated in both airspeed and thermal fields. Results of airflow pattern, centerline velocity and centerline temperature decay, velocity and temperature profile, airflow boundary layer and thermal boundary layer growth, floor velocity, and floor temperature difference were analyzed to establish semi-empirical prediction equations. Results also compared with previous researches to validate the physical behavior of air-jet. Data of centerline velocity decay showed similar airflow characteristics as isothermal air-jet with Archimedes number (Ar)<0.004, which performed as pseudo-isothermal airflow. Air-jet fell on entry with Ar>0.018. A single circulation airflow existed at 0.004
Keywords :
Slot-ventilated , Non-isothermal , Archimedes number , ventilation , Airflow characteristics
Journal title :
Building and Environment
Serial Year :
2007
Journal title :
Building and Environment
Record number :
409363
بازگشت