The performance of an open absorption-system, energized by low-grade heat such as insolation
and/or waste heat, has been investigated.This combined evaporative cooler (CEC) [i.e.
an indirect evaporative cooler (IEC) together with a direct evaporative-cooler (DEC)] was
used to cool the air.A computer simulation of the cooling cycle was devised, so that the performance
characteristics of the system could be predicted for a range of operating conditions:
the influences of various design-parameters on the coefficient of performance (COP) were also
evaluated.The COP of the CEC system was at least 20% greater than those achieved when
employing either the IEC or DEC systems alone.