• Title of article

    A method for the indication of power transformer saturation

  • Author/Authors

    D. Tousignant، نويسنده , , L. Bolduc، نويسنده , , A. Dutil، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1996
  • Pages
    6
  • From page
    115
  • To page
    120
  • Abstract
    DC currents flowing from the earth cause many Hydro-Québec transformers to saturate due to geomagnetically induced currents (GICs) or monopolar operation of HVDC systems with ground return. The resulting voltage distortion may affect the operation of control systems. This paper offers an explanation of the internal behavior of currents generated in the presence of DC currents. It also contains a harmonic analysis of these currents together with a detailed study of the magnetizing current. In saturation, a transformer core acts as a source of current generating harmonics, some of which will flow directly toward the primary and secondary windings. On the basis of these observations, the paper proposes a measurement method for obtaining the parameters needed to calculate a reliable indicator of the state of saturation of transformers. The method is based on the difference between the primary and secondary currents and on amplitude readings of the second and fourth harmonics.
  • Keywords
    transformers , Saturable cores , Geomagnetically induced current (GIC) , Magnetic storms , Harmonic distortion
  • Journal title
    Electric Power Systems Research
  • Serial Year
    1996
  • Journal title
    Electric Power Systems Research
  • Record number