Title of article
An air-conditioning unit with a zeotropic mixture controlled by a distillation column
Author/Authors
Yang Zhao، نويسنده , , Ma Yitai، نويسنده , , ZHAO SANYUAN، نويسنده , , LI YIE، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1998
Pages
8
From page
777
To page
784
Abstract
We describe a new air-conditioning and heat-pump system, which may be used to separate a refrigerant mixture efficiently and adjust the composition in the system with cooling- or heating-load changes. A dynamic model has been developed to analyze the transient behavior of the capacity-control system. An air conditioner equipped with a small distillation circuit has been tested. Increases in the SEERs (seasonal energy efficiency ratios) for the new composition-controlled system are 28.3 and 17.7% and capacity changes 57.3–91.8% and 71.5–101%, respectively, for R22/142b and R23/124.