Performance evaluation of hot-gas by-pass capacity control schemes for refrigeration and air-conditioning systems
Author/Authors :
M. Yaqub، نويسنده , , Syed M. Zubair، نويسنده , , Jameel-ur-Rehman Khan، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
19
From page :
543
To page :
561
Abstract :
The capacity control of a vapor-compression refrigeration system is investigated by injecting hot gas and liquid refrigerant into the suction side of the compressor. Three different possibilities for the by-pass schemes are investigated for HFC-134a by considering finite size of the components that are used in the refrigeration systems. The model considers the finite-temperature difference in the heat exchangers, thus allowing the variations in the condenser and evaporator temperatures with respect to capacity and external-fluid inlet temperatures. It is demonstrated that the compressor discharge temperatures increase significantly when the hot-gas from the compressor discharge is extracted and injected (without any liquid injection) directly into the suction side of the compressor. A comparative study is also performed of these schemes in terms of the system coefficient of performance (COP), operating temperatures and the refrigerant by-pass fraction as a function of the percentage capacity reduction.