Title of article :
A pre-cooling Munters environmental control desiccant cooling cycle in combination with chilled-ceiling panels
Author/Authors :
L. Z. Zhang، نويسنده , , J. L. Niu، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
18
From page :
275
To page :
292
Abstract :
Desiccant cooling is efficient in latent cooling, whereas chilled-ceiling is efficient for sensible cooling. In this paper, a new desiccant cooling system, a pre-cooling Munters environmental control (PMEC) cycle is proposed, which combines with chilled-ceiling panels. The mathematical model of the system is provided and used to predict the system performance under South-east China weather conditions using hour-by-hour calculations. The results indicate that chilled-ceiling combined with desiccant cooling could save up to 40% of primary energy consumption, in comparison with a conventional constant volume all-air system. More interestingly, more than 99% of annual operating hours for desiccant regeneration could be accomplished by low-grade heat of less than 80 °C with the new cycle, while 30% annual operating hours need heat higher than 80 °C with the old MEC cycle.
Journal title :
Energy
Serial Year :
2003
Journal title :
Energy
Record number :
416276
Link To Document :
بازگشت