• Title of article

    A pre-cooling Munters environmental control desiccant cooling cycle in combination with chilled-ceiling panels

  • Author/Authors

    L. Z. Zhang، نويسنده , , J. L. Niu، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    18
  • From page
    275
  • To page
    292
  • Abstract
    Desiccant cooling is efficient in latent cooling, whereas chilled-ceiling is efficient for sensible cooling. In this paper, a new desiccant cooling system, a pre-cooling Munters environmental control (PMEC) cycle is proposed, which combines with chilled-ceiling panels. The mathematical model of the system is provided and used to predict the system performance under South-east China weather conditions using hour-by-hour calculations. The results indicate that chilled-ceiling combined with desiccant cooling could save up to 40% of primary energy consumption, in comparison with a conventional constant volume all-air system. More interestingly, more than 99% of annual operating hours for desiccant regeneration could be accomplished by low-grade heat of less than 80 °C with the new cycle, while 30% annual operating hours need heat higher than 80 °C with the old MEC cycle.
  • Journal title
    Energy
  • Serial Year
    2003
  • Journal title
    Energy
  • Record number

    416276