• Title of article

    Energy saving possibilities with cooled-ceiling systems

  • Author/Authors

    J. Niu، نويسنده , , J. v. d. Kooi، نويسنده , , H. v. d. Rhee، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1995
  • Pages
    12
  • From page
    147
  • To page
    158
  • Abstract
    Based on hour-by-hour simulation studies, this paper presents the annual energy consumption characteristics of water-panel type cooled-ceiling systems in comparison with conventional all-air systems. In particular, some unique energy saving measures associated with cooled-ceiling systems are numerically studied. The results indicate that a cooled-ceiling system can save much of the fan energy required in all-air systems, and that in the temperate Dutch climate, the system has a compatible energy performance with a VAV (variable air volume) system for office-building cooling purposes. The energy saving possibilities studied include using ceiling water to pre- or re-heat ventilation air and using a cooling tower for free cooling. The paper also demonstrates the possibilities of using a simulation technique to estimate non-conventional energy efficient system designs.
  • Keywords
    Energy Savings , Cooled-ceiling systems
  • Journal title
    Energy and Buildings
  • Serial Year
    1995
  • Journal title
    Energy and Buildings
  • Record number

    418845