Title of article
Energy and peak power savings potential of radiant cooling systems in US commercial buildings
Author/Authors
Corina Stetiu، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1999
Pages
12
From page
127
To page
138
Abstract
The paper describes a parametric study developed to estimate the energy and peak power savings potential of radiant cooling systems in commercial buildings in the US. The study is based on the numerical modeling of a radiant cooling system and an all-air system at different locations in the US. The results show that a building equipped with a radiant cooling system can be operated in any US climate with low risk of condensation. For the office space examined in the study, employing a radiant cooling system instead of a traditional all-air system can save on average 30% of the energy consumption and 27% of the peak power demand due to space conditioning. The savings potential is climate-dependent, and is larger in retrofitted buildings than in new construction.
Keywords
Peak power , Radiant cooling system , Commercial building
Journal title
Energy and Buildings
Serial Year
1999
Journal title
Energy and Buildings
Record number
419040
Link To Document