• Title of article

    Real heat recovery with air handling units

  • Author/Authors

    C. -A. Roulet، نويسنده , , F. D. Heidt، نويسنده , , F. Foradini، نويسنده , , M. -C. Pibiri، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2001
  • Pages
    8
  • From page
    495
  • To page
    502
  • Abstract
    More and more air handling units are equipped with heat recovery systems, with the aim of decreasing the energy use in buildings for heating and cooling. The efficiency of the heat recovery system is often used to calculate the energy saving. However, air-handling units do not always function as planned. In particular, parasitic shortcuts and leakage may decrease dramatically the efficiency of ventilation and heat recovery. In addition, these units need electrical energy for fans, which may be more precious than saved heat. Measurements, using tracer gas dilution technique have detected various malfunctions in several units.
  • Keywords
    Air handling units , Efficiency , Heat recovery
  • Journal title
    Energy and Buildings
  • Serial Year
    2001
  • Journal title
    Energy and Buildings
  • Record number