Title of article :
Theoretical and computational analysis of closed wet cooling towers and its applications in cooling of buildings
Author/Authors :
Ala Hasan، نويسنده , , Piia Lamberg and Kai Sirén، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
10
From page :
477
To page :
486
Abstract :
Theoretical analysis and computational modelling of closed wet cooling towers (CWCTs) are presented. Experimental measurements for performance of a prototype tower are used to define the tower transfer coefficients. Tower flow rates and number of tubes and rows are optimised for the required cooling load and to achieve a high coefficient of performance (COP). The performance of a cooling system used to cool office buildings is simulated using the transient system (TRNSYS) simulation environment. The cooling system consisted of a CWCT, chilled ceilings, pumps and a fan. A control strategy, including night cooling, is introduced in the simulation. The results indicate efficient performance and high COP values for the system.
Keywords :
Tower model , simulation , Cooling Tower , Chilled ceiling
Journal title :
Energy and Buildings
Serial Year :
2002
Journal title :
Energy and Buildings
Record number :
419256
Link To Document :
بازگشت