Title of article :
Energy conservation potential, HVAC installations and operational issues in Hellenic airports
Author/Authors :
C. A. Balaras، نويسنده , , E. Dascalaki، نويسنده , , A. Gaglia، نويسنده , , K. Droutsa، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
16
From page :
1105
To page :
1120
Abstract :
This paper presents an overview of the results from a recently completed study on the assessment of the characteristics, current energy consumption and the potential for energy conservation in 29 Hellenic airports. The average annual total energy consumption at the airport terminals is 234 kWh/m2. A more detailed investigation for three representative airports, at different climatic zones, was also performed. Data was collected through energy audits of the three terminal buildings, thermal infrared (IR) inspections of the building envelopes and HVAC installations, an assessment of indoor environmental quality (IEQ) through long term monitoring and spot measurements of indoor thermal and visual conditions, as well as personnel and passenger questionnaires. The collected information was used to perform a detailed analysis using thermal simulations for assessing specific measures to reduce energy use without compromising comfort, and to identify possible actions for improving IEQ. For the three airports, potential energy savings range at 15–35%, while improving and maintaining indoor environmental quality.
Keywords :
Audits , energy conservation , airports , Indoor environmental quality , HVAC
Journal title :
Energy and Buildings
Serial Year :
2003
Journal title :
Energy and Buildings
Record number :
419419
Link To Document :
بازگشت