Title of article :
Effective cowshed insulating and ventilation system parameters
Author/Authors :
B. Kavolelis، نويسنده , , I. Sateikis، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
5
From page :
969
To page :
973
Abstract :
Using the rules of thermophysics, aerodynamics and mathematics, it was analysed how the constructional and technological factors of the building influence the parameters of effective insulating rate and ventilation. It was composed the formula for calculating the effective coefficient of the heat transmission of the external barrier. This formula integrally evaluates the heat balance of the building, incondensable water vapour condition, constructional and technological factors. Using the composed formula, it was established that after increasing the amount of animal total heat flow to the ground area unit from 90 to 150 W/m2, it would be rational to reduce the coefficient of the heat transmission from 5.0 to 2.3 W/(m2 K). After reducing the coefficient of the heat transmission, the indoor air temperature during the cold period increases about 7 °C. It was composed the formula for calculating the parameters of cowshed ventilation system according to outside air temperature. According to calculations, when the outside air temperature is dropping from 20 to −20 °C, it would be rational to reduce 85% of the vent area.
Keywords :
Heat transmission coefficient , Ventilation system parameter , Mathematical dependence , Temperature difference
Journal title :
Energy and Buildings
Serial Year :
2004
Journal title :
Energy and Buildings
Record number :
419520