Title of article :
Experimental study of a heat pump system with flash-tank coupled with scroll compressor
Author/Authors :
Guoyuan Ma، نويسنده , , Hui-Xia Zhao، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Abstract :
A heat pump system with a flash-tank coupled with a scroll compressor is compared with a system with a sub-cooler. The heat pump performance was measured experimentally. The heating capacity of the prototype decreased as the evaporation temperature decreased, but the decrease was much slower than that of a conventional air-source heat pump. The power input varied slightly with the evaporation temperature. The heat pump system with a flash-tank is more efficient than the system with a sub-cooler at low ambient temperatures, so it will be very useful as a small capacity air-source heat pump.
Keywords :
Heat pump , Economizer , Scroll compressor , Flash-tank
Journal title :
Energy and Buildings
Journal title :
Energy and Buildings