• Title of article

    New cooling regulation technology of secondary cooling station in DCS

  • Author/Authors

    Xuan Zhou، نويسنده , , Jun-wei Yan، نويسنده , , Dongsheng Zhu، نويسنده , , Lie-quan Liang، نويسنده , , Fei-long Liu، نويسنده , , Jun-xi Lei، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2008
  • Pages
    5
  • From page
    1171
  • To page
    1175
  • Abstract
    In this paper, a kind of new control technology of secondary cooling station (constant flow rate/variable temperature difference) in district cooling system (DCS) is proposed in view of serial consequences including low efficiency and high operating cost caused by low temperature of supply water in DCS. This technology has been applied in DCS of Guangzhou University City. The result has already indicated that such technology can increase the supply and return temperatures of buildings, return water temperature of primary side in the plate heat exchanger unit, moreover, the efficiency of both the chiller and the whole system are improved significantly.
  • Keywords
    Refrigeration efficiency , District cooling system , Cold regulation technology of constant flow rate/variable temperature difference
  • Journal title
    Energy and Buildings
  • Serial Year
    2008
  • Journal title
    Energy and Buildings
  • Record number

    420113