    Cooling load reduction by using thermal mass and night ventilation

  • Author/Authors

    Lina Yang، نويسنده , , Yuguo Li، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2008
  • Pages
    7
  • From page
    2052
  • To page
    2058
  • Abstract
    We provide a quantitative understanding of the relationship between thermal mass and cooling load, i.e. the effect of thermal mass on energy consumption of air-conditioning in office buildings. A simple office-building model with air-conditioning at daytime and free cooling at nighttime is analyzed in detail to quantify the hourly and overall variation of cooling load of air-conditioning. As an important parameter, an increase of time constant can effectively reduce the cooling load, by as much as more than 60% when the time constant is more than 400 h. However, when the time constant is larger than 1000 h, a further increase may slightly increase the cooling load, as a too large time constant may also postpone the heat release of thermal mass until the daytime. For the most effective reduction of cooling load, the interior and exterior convective heat transfer numbers need to be matched.
  • Keywords
    Cooling load ratio , Night ventilation , Air-conditioning , Thermal mass , Cooling load
  • Journal title
    Energy and Buildings
  • Serial Year
    2008