Title of article :
Condensation of a zeotropic CFC 114-CFC 113 refrigerant mixture in the annulus of a double-tube coil with an enhanced inner tube
Author/Authors :
Shigeru Nozu، نويسنده , , Hiroshi Honda، نويسنده , , Shin Nishida، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1995
Pages :
8
From page :
364
To page :
371
Abstract :
Local heat transfer and pressure drop measurements were made during condensation of a zeotropic CFC114-CFCll3 refrigerant mixture in the annulus of a double-tube coil consisting of three U-bends and four straight lengths. The inner tube is a 19.1-mm O.D. corrugated copper tube with wire fins soldered onto the outer surface and the inner diameter of the outer duct is 25.0 mm. The vapor-phase mass transfer coefficient exhibited a sawtooth behavior with the U-bends showing higher coefficients than the straight lengths. The frictional pressure gradient data agreed well with a previously developed empirical equation for the condensation of pure refrigerants. A prediction method for the condensation heat transfer rate was proposed on the basis of the correlations of the vapor-phase mass transfer coefficient and heat transfer coefficient of the condensate film. The heat transfer data were correlated by the present method to a mean absolute deviation of 12.9%.
Keywords :
Condenser , heat transfer enhancement , zeotropic refrigerant mixture , Heat transfer , double-tube coil , pressure drop