Title of article :
Measurement of the Specific Enthalpy of Vaporization on 1,1,1,2-Tetrafluoroethane in the Temperature Range from 180 to 240 K
Author/Authors :
W. Blanke، نويسنده , , G. Klingenberg and F. Weber ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Pages :
10
From page :
653
To page :
662
Abstract :
An apparatus is described which is capable of measuring the enthalpy of vaporization in the temperature range from 100 to 250 K. The sample (R134a; purity, at least 99.999%) is located in the measuring cell at the saturated vapor pressure, p = ps. A control circuit allows p to be kept constant by opening a motor-operated valve to a weighing cylinder after having switched on the electrical measuring cell heater. During the experiment, the temperature is kept constant within a l0mK. In the range 180 to 230 K, the data for R134a are compared with calculated values from the fundamental equation given by Tillner-Roth and Baehr, which is recommended by Annex 18 of the IInternational Energy Agency (IEA) as an iInternational standard. Good agreement within a standard uncertainty of 1.6x 10- 3 is obtained. At temperatures of only 10 K above the triple-point temperature, the enthalpy of vaporization calculated from the Clausius-Clapeyron equation shows considerable uncertainty due to the determination of the small vapor pressure. It is chiefly in this range that it is advantageous to have the new apparatus.
Keywords :
Clausius-Clapeyron equation , R134a , enthalpy of vaporization , 1 , 1 , 1 , 2-tetrafluoroethane. , 1
Journal title :
International Journal of Thermophysics
Serial Year :
1998
Journal title :
International Journal of Thermophysics
Record number :
426388