• Title of article

    The use of Hg/Hg2SO4 reference electrodes in valve-regulated lead/acid cells

  • Author/Authors

    Michael K. Carpente، نويسنده , , Dawn M. Bernardi، نويسنده , , John A. Wertz، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1996
  • Pages
    8
  • From page
    15
  • To page
    22
  • Abstract
    Reference electrode and gas flow measurements were used to characterize the discharge and charge behavior of a valve-regulated lead/acid cell. The implementation of a Hg/Hg2SO4 reference electrode suitable for this type of cell is described. The nature of the reference electrode gives rise to liquid junction potentials. The liquid junction potential theory is reviewed and applied to correct the measured half-cell potentials during cell operation. Corrections of over 60 mV were required for measurements at the end of discharge and beginning of charge. The PbO2 electrode is shown to control the decrease in cell voltage during discharge; that is, discharge capacity is limited by the PbO2 electrode. In contrast, during galvanostatic charge to a charge-voltage lid, the final cell voltage increase is controlled by the Pb electrode.
  • Keywords
    Hg/Hg2SO4 reference electrodes , Gassing , Valve-regulated lead/acid batteries
  • Journal title
    Journal of Power Sources
  • Serial Year
    1996
  • Journal title
    Journal of Power Sources
  • Record number

    438710