• Title of article

    Advances in VRLA battery technology for telecommunications

  • Author/Authors

    Sudhan S. Misra، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2007
  • Pages
    9
  • From page
    40
  • To page
    48
  • Abstract
    Wide scale use of the newly emergent VRLA (valve-regulated lead-acid) battery in telecommunication applications and the subsequent problems encountered early in their deployment history spurred intense efforts to improve the design as a continuous endeavor. After implementing improvements to battery placement and containment design to prevent the sudden onset of thermal runaway, the focus of the development work has been on cell internals. These include improved grid and strap alloys, superior AGM (absorbent glass mat) separator that retains compression in the cell, use of beneficial additives to the active materials and the need to avoid contaminants that promote detrimental side reactions. These improvements are now resulting in a vastly superior VRLA experience in the telecommunication applications. To further improve the reliability demanded by todayʹs communication and internet environment VRLA battery installations should include continuous cell/module and system monitoring similar to that incorporated in competing advanced battery systems under development.
  • Keywords
    Telecommunication , VRLA , Grid alloys , AGM separators , Reliability
  • Journal title
    Journal of Power Sources
  • Serial Year
    2007
  • Journal title
    Journal of Power Sources
  • Record number