Title of article
Phase-time analysis of the leakage impulse current of faulty line-post pin insulators
Author/Authors
C.J.، Kim, نويسنده , , J.A.، Momoh, نويسنده , , Lee، Heung-Jae نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2003
Pages
-322
From page
323
To page
0
Abstract
Leakage impulse current of the faulty insulators was experimentally studied. The leakage impulse current was characterized in terms of the phase-time base of the applied voltage. The study showed that the leakage impulse is observed only in a distinct location in phase-time space. Based on the findings, prioritized maintenance scheduling was proposed, which could be used for status monitoring of insulators and distribution feeders.