• Title of article

    Deriving an equivalent circuit of transformers insulation for understanding the dielectric response measurements

  • Author/Authors

    T.K.، Saha, نويسنده , , P.، Purkait, نويسنده , , F.، Muller, نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2005
  • Pages
    9
  • From page
    149
  • To page
    157
  • Abstract
    Preventive diagnosis and maintenance of transformers have become more and more popular in recent times in order to improve the reliability of electric power systems. Dielectric testing techniques such as return voltage measurement (RVM) and polarization-depolarization current (PDC) measurement are being investigated as potential tools for condition assessment of transformer insulation. A better understanding and analysis of the dielectric test results are only possible with a clear understanding of the physical behavior of the insulation system in response to moisture and aging. A circuit model, which describes the dielectric behavior of the transformerʹs main insulation system, has been parameterized in this paper. The values of the parameters of the model have been identified from the dielectric tests. A correlation has been developed between the physical condition of the insulation and the equivalent model parameters that enable a clear and transparent interpretation of the dielectric test results.
  • Keywords
    Power-aware
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2005
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    61680