• Title of article

    Fuzzy logic-based relaying for large power transformer protection

  • Author/Authors

    Shin، Myong-Chul نويسنده , , Park، Chul-Won نويسنده , , Kim، Jong-Hyung نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    7
  • From page
    718
  • To page
    724
  • Abstract
    Power transformer protective relay should block the tripping during magnetizing inrush and rapidly operate the tripping during internal faults. The frequency environment of power system has been made more complicated and the quantity of 2nd frequency component in inrush state has been decreased because of the improvement of core steel. Then, traditional approaches will likely be maloperated in the case of magnetizing inrush with low second harmonic component and internal faults with high second harmonic component. This paper proposes a new relaying algorithm to enhance the fault detection sensitivities of conventional techniques by using a fuzzy logic approach. The proposed fuzzy-based relaying algorithm consists of flux-differential current derivative curve, harmonic restraint, and percentage differential characteristic curve. The proposed relaying was tested with relaying signals obtained from Salford EMTP simulation package and showed a fast and accurate trip operation.
  • Keywords
    (alpha)-Amylase , histidine modification , Thermophilic bacteria , hydrolytic enzyme , Bacillus subtilis , enzyme purification
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2003
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number