Title of article :
Study of abnormal electrical phenomena effects on GSU transformers
Author/Authors :
Liu، Yilu نويسنده , , Dong، Xuzhu نويسنده , , S.، Rosado, نويسنده , , Wang، Nien-Chung نويسنده , , E.-L.، Line, نويسنده , , Guo، Tzong-Yih نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Abstract :
Three generator-step-up (GSU) transformers successively failed in a large pumped storage plant, resulting in a considerable economic loss for the utility. A comprehensive investigation was done to find out the possible failure causes. Several aspects are considered in this study, including switching transients resulting from routine switching operations, lightning overvoltages, and harmonics and spikes due to static frequency converter (SFC) operation. The study showed that circuit breaker and disconnector restriking may affect transformer insulation due to their frequent occurrence, gas insulated switching gear (GIS) side surge arresters provide inadequate lightning protection to GSU transformers, and SFC operation has little effect on transformer insulation. This paper presents the simulation results. Methods to lower the lightning transients at the transformer terminals were provided and implemented.
Keywords :
(alpha)-Amylase , Bacillus subtilis , enzyme purification , histidine modification , hydrolytic enzyme , Thermophilic bacteria
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY