• Title of article

    Clarification and measurements of high frequency harmonic resonance by a voltage sourced converter

  • Author/Authors

    K.، Temma, نويسنده , , F.، Ishiguro, نويسنده , , N.، Toki, نويسنده , , I.، Iyoda, نويسنده , , J.J.، Paserba, نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2005
  • Pages
    8
  • From page
    450
  • To page
    457
  • Abstract
    This work presents the clarification and measurements of a high-order harmonic resonance phenomenon for voltage sourced converters. When a voltage sourced converter is connected to a power system through a cable, there is a possibility that small, high frequency, harmonic voltages due to the converter are magnified by series and parallel resonances. The cause of the high-order harmonic resonance is investigated and clarified in this paper by analysis using EMTP. It is shown that this high frequency phenomenon can be strongly attenuated and will not cause any problems in a field installation if measures are taken a priori to avoid its impacts. Additionally, the phenomenon is verified by field tests of an actual installation showing that high-order harmonic resonance can occur and is a practical matter to be dealt with. The measurements for the resonance phenomenon are included in this paper. Furthermore, it is shown that this high-order harmonic resonance can be predicted by power system analysis in advance. The procedure of the analysis is investigated and presented here.
  • Keywords
    Power-aware
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2005
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number