• Title of article

    A study on transformer loading in Manitoba-peak-load ambient temperature

  • Author/Authors

    Li، Xin نويسنده , , G.، Zielke, نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    8
  • From page
    1249
  • To page
    1256
  • Abstract
    It is shown that the hourly ambient temperature and load of a substation transformer in Manitoba, observed over the three-month winter or summer time window, are governed by the normal distribution, respectively, and they jointly follow the bivariate normal distribution. Based on this, a rigorous model for the peak-load ambient temperature (i.e., the ambient temperature at the time when the winter or summer peak-load of the transformer occurs) is developed. This makes it possible to accurately determine the peak load capability of the transformer if its historical hourly ambient temperature and load data are available.
  • Keywords
    Thermophilic bacteria , (alpha)-Amylase , Bacillus subtilis , enzyme purification , hydrolytic enzyme , histidine modification
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2003
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number