Title of article :
A Novel Approach to Study the Performance of Finned-Tube Heat Exchangers under Frosting Conditions
Author/Authors :
Bendaoud، A.L. نويسنده , , Ouzzane، M. نويسنده , , Aidoun، Z. نويسنده , , Galanis، N. نويسنده ,
Issue Information :
دوفصلنامه با شماره پیاپی 8 سال 2011
Abstract :
Frost accumulation due to moist air flowing on a refrigeration coil cold surface impacts negatively on performance.
The frost layer growth has an insulating effect in terms of heat transfer and causes the increase of the air pressure
drop by blocking the free flow area across the coil. In this paper a new modeling approach, accounting for heat and
mass transfer as well as the hydrodynamics of the problem, is proposed. A related FORTRAN program was
developed, allowing the study of a large range of complex refrigerant circuit configurations. This model predicts the
dynamic behavior of a refrigeration coil under dry and frosting conditions. Comparisons were made based on the
frost mass accumulation and pressure drop across the coil and the results were found to agree reasonably well with
experimental results reported in the literature. The model was then applied to study an evaporator typically employed
in supermarkets. In terms of refrigerant temperature glide, it was shown that the glide decrease with time because of
the decrease of the refrigeration capacity of the coil during the frosting. Further, the air pressure drop is strongly
affected by the variation of the free flow area.
Journal title :
Journal of Applied Fluid Mechanics (JAFM)
Journal title :
Journal of Applied Fluid Mechanics (JAFM)