Author/Authors :
Mazlumi، Kazem نويسنده Electrical Engineering Department, University of Zanjan, Zanjan, Iran , , Azari، Mehdi نويسنده Electrical Engineering Department, University of Zanjan, Zanjan, Iran , , Beheshti، Sasan نويسنده Electrical Engineering Department, University of Zanjan, Zanjan, Iran ,
Abstract :
The standards of power system monitoring,
control and protection are elevated by Phasor
Measurement Units (PMUs) as an auspicious tool. It is
the purpose of this paper to determine the optimal number
and locations of PMUs so as to make the system
measurement model observable and also estimate the
power system state. The proposed modelling approach
which models PMU placement as an integer linear
programming problems, is extended and generalized to
satisfy various aspects of optimal phasor measurement
unit (PMU) placement problem. Cases with and without
zero injection measurements are considered. The optimal
PMU placement problem can be achieved by using linear
constraints. This implies that optimal PMU placement
problem with zero injection busses can now be solved by
standard ILP solvers. Subsequently, we also develop a
simple and an effective methodology to handle single
PMU outage as well as single line outage in the system.
The robust performance of the proposed approach is
confirmed on the IEEE 9, 14 and 57-bus test systems.
The results obtained in this paper are compared with
those published before in literature.